3M
™
MediumVoltage Solutions
up to 33 kV
56
3M
™
Transition Joint Kits
Joints are specifically designed and optmised for New Zealand conditions, and meet or exceed the requirements of IEC 60502-4.
3M
™
QS2000E Three Core Transition Straight Joint Kit
11 kV Cable
Cable:
Three core armoured PILC to Three Single Core XLPE (Polymeric Insulation, Copper Wire Screened
∞
, Non-Armoured)
Contents:
Each kit contains components to joint three cores and is supplied with mechanical connectors
3M
™
Cold Shrink QS2000E Three Core Trifurcating Cable Jointing Kits
Single Core Cable - 11 kV
Cable:
Polymeric Insulation, Copper Wire Screened, Non-Armoured
Contents:
Each kit contains components for three cores
Cable:
Three core armoured PILC to Three Core XLPE (Polymeric Insulation, Copper Wire Screened
∞
, Non-Armoured)
Contents:
Each kit contains components to joint three cores and is supplied with mechanical connectors
Voltage
Paper Insulated Cable
Polymeric Insulated Cable
BIL kV
3M Kit
No. Cores
Cable Size mm
2
Cable Insulation Range
Min. mm
No. Cores
Cable Size mm
2
Cable Insulation
Range mm
11 kV
3
16 - 95
8 - 12
1
25* - 95
14.6 - 25.2
95
92-FS 213-3-1-NZ
95 - 300
17.4
95**
18 - 36.8
95
92-FS 233-3-1S-NZ
95 - 300
17.4
185 - 300
19.1 - 36.8
95
92-FS 233-3-1-NZ
Voltage
Paper Insulated Cable
Polymeric Insulated Cable
BIL kV
3M Kit
No. Cores
Cable Size mm
2
Cable Insulation Range
Min. mm
No. Cores
Cable Size mm
2
Cable Insulation
Range mm
11 kV
3
16 - 95
8 - 12
3
25* - 95
14.6 - 25.2
95
92-FS 213-3-3-NZ
95 - 300
17.4
95** - 300
19.1 - 36.8
95
92-FS 233-3-3-NZ
Cable Size mm
2
Cable Insulation Range
Min. mm
BIL kV
3M Kit
11 kV / 3 core
11 kV / 1 core
25* - 95
25* - 95
14.6 - 25.2
95
92-AS 610-3-1-NZ-1
95* - 300
95* - 185
19.1 - 36.8
95
92-AS 620-3-1S-NZ-4
95* - 300
185 - 300
19.1 - 36.8
95
92-AS 620-3-1-NZ-4
*Adaptor tubes (included in kit) required for 25 mm² polymeric insulated cable
**Adaptor tubes (included in kit) required for 95 mm² polymeric insulated cable
*Adaptor tubes (included in kit) required for 25 mm² polymeric insulated cable
**Adaptor tubes (included in kit) required for 95 mm² polymeric insulated cable
*Adaptor kits required (not included in kits)
Transition Joint Kits, Termination Barrier Boots and Electrostatic Animal Guard
3M
™
Termination Barrier Boots
3M Barrier Boots are suitable for both cold shrink and heat shrink medium voltage terminations and cover a wide
range of cable sizes.
Product
3M Order Code
Description
Features
Application
Range
Voltage Rating Availability
92-EE 717-1 TE100052030
15 kV Inline or Right Angle Barrier Boot
(3 cores/kit)
• One piece push on EPDM boot
• Suitable for straight and right angle application
• Easy installation
50 - 300 mm
2
up to 15 kV
AU, NZ
MB63-NZ
11 kV Inline Cold Shrink Barrier Boot
(3 cores/kit)
• Cold shrink technology
• Easy installation
• Track resistant EPDM material
up to 630 mm
2
up to 11 kV
NZ
MB61-NZ
11 kV Universal Taped System
(3 cores/kit)
• Versatile taped barrier boot system
• Inline and right angle application
up to 1000 mm
2
up to 11 kV
NZ
3M
™
Electrostatic Animal Guard
This is a patented electrostatic barrier that attaches to energised electrical insulators/bushings rated up to 35 kV. The
3M Electrostatic Animal Guard consists of rugged plastic with metal spokes radiating outward.When an animal touches
the spokes, it receives an electric shock, similar to those generated by electrified livestock fences. The animal is not
injured and power service is not interrupted.
Product
3M Order Code
Insulator Neck Diameter Range
Voltage
GG-1525
80610981120
38 - 64 mm
Up to 35 kV
GG-2545
80610981138
64 - 114 mm
Up to 35 kV
GG-4565
80610981146
114 - 165 mm
Up to 35 kV
Note:
Insulator neck diameter
range is defined as the diameter of
the insulator in between the skirts