3M
™
MediumVoltage Solutions
up to 33 kV
48
Medium Voltage Cold Shrink Cable Termination Kits
(Australia)
Final determining factors are cable jacket and insulation diameters.
Voltage
Description
No. Cores
Cable
Size
mm
2
Cable
Insulation
Range
mm
Jacket
Diameter
Range
mm
BIL
kV
NON-ARMOURED or
ARMOURED CABLE
3M Kit
3M Order Code
3.3 kV
Indoor
3
25 - 70
11.2 - 16.5
36 - 61
95
92-EB 60-3-AU
AE010592473
70 - 185
14.2 - 22.1
36 - 61
95
92-EB 61-3-AU
AE010592481
95 - 185
16.5 - 22.1
49 - 79
95
92-EB 62-3-AU
AE010592499
185 - 400
19.8 - 33.0
49 - 79
95
92-EB 63-3-AU
AE010592507
240 - 400
22.0 - 33.0
64 - 110
95
92-EB 64-3-AU
AE010592515
Outdoor
3
50 - 150
14.2 - 22.1
36 - 61
125
93-EB 60-3-AU
AE010592523
95 - 150
16.0 - 28.4
36 - 61
125
93-EB 61-3-AU
AE010592531
185 - 300
16.0 - 28.4
49 - 79
125
93-EB 62-3-AU
AE010592549
400 - 500
21.3 - 35.0
64 - 110
125
93-EB 63-3-AU
AE010592556
6.6 kV
Indoor
3
25 - 70
11.2 - 16.5
36 - 61
95
92-EB 60-3-AU
AE010592473
70 - 150
14.2 - 22.1
36 - 61
95
92-EB 61-3-AU
AE010592481
95 - 150
16.5 - 22.1
49 - 79
95
92-EB 62-3-AU
AE010592499
185 - 300
19.8 - 33.0
49 - 79
95
92-EB 63-3-AU
AE010592507
240 - 400
22.0 - 33.0
64 - 110
95
92-EB 64-3-AU
AE010592515
Outdoor
3
50 - 150
14.2 - 22.1
36 - 61
125
93-EB 60-3-AU
AE010592523
95 - 150
16.0 - 28.4
36 - 61
125
93-EB 61-3-AU
AE010592531
185 - 300
16.0 - 28.4
49 - 79
125
93-EB 62-3-AU
AE010592549
400 - 500
21.3 - 35.0
64 - 110
125
93-EB 63-3-AU
AE010592556
11 kV
Indoor
3
10 - 25
11.2 - 16.5
36 - 61
95
92-EB 60-3-AU
AE010592473
35 - 70
14.2 - 22.1
36 - 61
95
92-EB 61-3-AU
AE010592481
70 - 95
16.5 - 22.1
49 - 79
95
92-EB 62-3-AU
AE010592499
120- 150
19.8 - 33.0
49 - 79
95
92-EB 63-3-AU
AE010592507
185 - 300
22.0 - 33.0
64 - 110
95
92-EB 64-3-AU
AE010592515
Outdoor
3
35
14.2 - 22.1
36 - 61
125
93-EB 60-3-AU
AE010592523
50 - 70
16.0 - 28.4
36 - 61
125
93-EB 61-3-AU
AE010592531
95 - 150
16.0 - 28.4
49 - 79
125
93-EB 62-3-AU
AE010592549
185 - 300
21.3 - 35.0
64 - 110
125
93-EB 63-3-AU
AE010592556
15 kV
Indoor
3
25 - 50
14.2 - 22.1
36 - 61
95
92-EB 61-3-AU
AE010592481
50 - 70
16.5 - 22.1
49 - 79
95
92-EB 62-3-AU
AE010592499
95 - 120
19.8 - 33.0
49 - 79
95
92-EB 63-3-AU
AE010592507
150 - 240
22.0 - 33.0
64 - 110
95
92-EB 64-3-AU
AE010592515
Outdoor
3
25
14.2 - 22.1
36 - 61
125
93-EB 60-3-AU
AE010592523
35 - 50
16.0 - 28.4
36 - 61
125
93-EB 61-3-AU
AE010592531
70 - 120
16.0 - 28.4
49 - 79
125
93-EB 62-3-AU
AE010592549
150 - 240
21.3 - 35.0
64 - 110
125
93-EB 63-3-AU
AE010592556
22 kV
Indoor
3
10 - 16
14.2 - 22.1
36 - 61
125
93-EB 60-3-AU
AE010592523
25 - 35
16.0 - 28.4
36 - 61
125
93-EB 61-3-AU
AE010592531
50 - 120
16.0 - 28.4
49 - 79
125
93-EB 62-3-AU
AE010592549
120 - 240
21.3 - 35.0
64 - 110
125
93-EB 63-3-AU
AE010592556
Outdoor
3
25 - 35
16.2 - 24.4
36 - 61
170
94-EB 61-3-AU
AE010592564
50 - 120
16.2 - 28.4
49 - 79
170
94-EB 62-3-AU
AE010592572
120 - 240
21.3 - 35.0
64 - 110
170
94-EB 63-3-AU
AE010592580
33 kV
Indoor
3
25 - 50
16.2 - 28.4
49 - 79
170
94-EB 62-3-AU
AE010592572
25 - 150
21.3 - 35.0
64 - 110
170
94-EB 63-3-AU
AE010592580
95 - 240
27.4 - 45.7
64 - 110
170
94-EB 64-3-AU
AE010592598
Outdoor
3
25 - 150
21.3 - 35.0
64 - 110
170
94-EB 63-4-AU
AE010592606
95 - 240
27.4 - 45.7
64 - 110
170
94-EB 64-4-AU
AE010592614
Cold Shrink QT-II Termination Kits for Three Core Cable (AU)
3M Cold Shrink QT-II Termination Kits
Three Core Cable - 3.3 kV to 33 kV
Cable:
Polymeric Insulation, Copper Wire Screened, Non-Armoured or Armoured
Contents:
Each kit will make one three core termination. Lugs not included.